Difference between revisions of "MCE firmware"

From MCEWiki
Line 1: Line 1:
{{Hierarchy header}}
 
 
 
= Critical Notes =
 
= Critical Notes =
 
* In v5+ firmware, if you update firmware on any readout card, the card doesn't reply to any command unless the Clock Card is also reprogrammed.
 
* In v5+ firmware, if you update firmware on any readout card, the card doesn't reply to any command unless the Clock Card is also reprogrammed.
Line 56: Line 54:
 
* [[ Upgrading From 4.x.x To 5.x.x Firmware ]] -- using SCUBA-2 as an example
 
* [[ Upgrading From 4.x.x To 5.x.x Firmware ]] -- using SCUBA-2 as an example
  
MCE Firmware Bugs/ Features Under Development has been moved to the [[intmce:MCE bugs]].
+
MCE Firmware Bugs/ Features Under Development has been moved to the [[intmce:MCE bugs]].<includeonly>{{#hierarchy-bottom:}}</includeonly><noinclude>
 +
This is the footer of a page that belongs to a hierarchy.
 +
</noinclude>
 +
 
  
 
= Firmware Development Tools =
 
= Firmware Development Tools =
Line 74: Line 75:
 
* [[ Using Python to Automate MAS ]]
 
* [[ Using Python to Automate MAS ]]
 
* [[ MCE: Helper programs ]]
 
* [[ MCE: Helper programs ]]
 
{{Hierarchy footer}}
 

Revision as of 14:28, 11 December 2011

Critical Notes

  • In v5+ firmware, if you update firmware on any readout card, the card doesn't reply to any command unless the Clock Card is also reprogrammed.
  • Always cleanly reset the MCE after a power-up or a reconfiguration! If not, MCE communication with the PC or Sync Box may not work. On MAS prompt, type: mce_reset_clean
  • After an mce_reset, not all of the DAC outputs are set to zero. In addition, values written to RAM-based registers are not reset. A full reconfiguration is required for a proper reset. You may power-cycle the MCE remotely if the MCE is equipped with a PSA (UBC switching supply) by issuing mce_cmd -x rs psc cycle_pow 1 and then mce_reset_clean

Releases

All firmware can be downloaded from http://e-mode.phas.ubc.ca/mce_firmware/. Release notes for each firmware release can be found below:

Firmware Upgrade Methods

There are two ways to upgrade the MCE firmware:

  1. Remote firmware update over the MCE fibre interface
  2. Using Altera-supplied Hardware/Software and MCE Front-panel Connector

MCE Features and How-To Guides

MCE Firmware Bugs/ Features Under Development has been moved to the intmce:MCE bugs. This is the footer of a page that belongs to a hierarchy.


Firmware Development Tools

MCE Scripting