MCE commands

From MCEWiki
Revision as of 18:50, 20 January 2010 by Bburger (talk | contribs) (Address Card (ac) Commands)

All Card (cc/rc#/bc#/ac) Commands

System (sys) Commands

Clock Card (cc) Commands

Readout Card (rc#) Commands

Bias Card (bc#) Commands

Address Card (ac) Commands

Parameter ID Physical Address Type Firmware Revision Parameters Description
-- 0x00 -- -- -- Reserved
row_order 0x01 wb/rb all row1,

row2, ...

This command is relevant when enbl_mux = 1 or 2. Read/write the row-addressing order. A sequence of up to 41 rows is specified at once. The row numbers that are specified with this command refer to the physical channel numbers on the Address Card. Note: After this command is issued, a “flx_lp_init” command must be issued to all the readout cards to discard previous PID-loop calculations and to clean out the rest of the data pipeline. Default = 0,0,0,…