Difference between revisions of "Special SQ1 Bias Commands"
From MCEWiki
Line 9: | Line 9: | ||
biases. This means the heater biases are applied by clock cycle #5. | biases. This means the heater biases are applied by clock cycle #5. | ||
+ | Note that these commands are only available in AC firmware 2.0.9 and 5.0.2. | ||
Here is a timing diagram of SQ1 Bias when enbl_mux = 3 | Here is a timing diagram of SQ1 Bias when enbl_mux = 3 | ||
[[File: ac_enbl_mux_3_scheme.png|400px]] | [[File: ac_enbl_mux_3_scheme.png|400px]] |
Revision as of 12:56, 20 January 2011
Address Card has a special multiplexing mode, enbl_mux = 3, when selected SQ1 Bias lines are turned on for an adjustable duration in the begining of a row visit, before the target SQ1 Bias for that row is turned on. The following parameters need to be set for this mode:
- bias_start
- heater_bias
- Upto 41 values that specify the magnitude of the SQ1-bias heating pulse in DAC units (0 to 16,383) during the initial heater_bias_len period of each row visit.
- heater_bias_len
- a single value that specifies the length of the SQ1-bias heating pulses at the beginning of every new row period. heater_bias_len is measured from the first clock cycle of each new row dwell time. However, it takes 4 clock cycles to apply all the heater
biases. This means the heater biases are applied by clock cycle #5.
Note that these commands are only available in AC firmware 2.0.9 and 5.0.2.
Here is a timing diagram of SQ1 Bias when enbl_mux = 3