Address Card has a special multiplexing mode, enbl_mux = 3, when selected SQ1 Bias lines are turned on for an adjustable duration in the begining of a row visit, before the target SQ1 Bias for that row is turned on. The following parameters need to be set for this mode:
+
Address Card has a special multiplexing mode, '''enbl_mux''' = 3. In this mode, selected SQ1 Bias lines are turned on for an adjustable duration in the begining of a row visit, before the target SQ1 Bias for that row is turned on. The DACS are updated with '''heater_bias''' values during the first '''heater_bias_len''' clock cycles, and with '''on_bias''' values for the remaining clock cycles of a row visit. The following parameters need to be set for this mode:
;bias_start
 
;heater_bias:
 
:Upto 41 values that specify the magnitude of the SQ1-bias heating pulse in DAC units (0 to 16,383).
 
  
;heater_bias_len:
+
;heater_bias
:a single value that specifies the length of the SQ1-bias heating pulses at the beginning of every new row period. heater_bias_len is measured from the first clock cycle of each new row dwell time.  However, it takes 4 clock cycles to apply all the heater
+
:Upto 41 values that specify the magnitude of the SQ1-bias heating pulse in DAC units (0 to 16,383) during the initial heater_bias_len period of each row visit.
biases.  This means the heater biases are applied by clock cycle #5.   
+
 
 +
;heater_bias_len
 +
:a single value that specifies the length of the SQ1-bias heating pulses at the beginning of every new row period. heater_bias_len is measured from the first clock cycle of each new row dwell time.  However, it takes 4 clock cycles to apply all the heater biases.  This means the heater biases are applied by clock cycle #5.   
 +
 
 +
;enbl_mux
 +
set enbl_mux = 3 for this special multiplexing mode.
 +
 
 +
Note 1: these commands are only available in AC firmware 2.0.9 and 5.0.2. <br>
 +
Note 2: bias_start parameter is not taken into account in this special multiplexing mode.
  
 
Here is a timing diagram of SQ1 Bias when enbl_mux = 3
 
Here is a timing diagram of SQ1 Bias when enbl_mux = 3
 
[[File: ac_enbl_mux_3_scheme.png|400px]]
 
[[File: ac_enbl_mux_3_scheme.png|400px]]
 +
 +
[[Category:Address Card Firmware]]

Latest revision as of 18:55, 31 August 2016

Address Card has a special multiplexing mode, enbl_mux = 3. In this mode, selected SQ1 Bias lines are turned on for an adjustable duration in the begining of a row visit, before the target SQ1 Bias for that row is turned on. The DACS are updated with heater_bias values during the first heater_bias_len clock cycles, and with on_bias values for the remaining clock cycles of a row visit. The following parameters need to be set for this mode:

heater_bias
Upto 41 values that specify the magnitude of the SQ1-bias heating pulse in DAC units (0 to 16,383) during the initial heater_bias_len period of each row visit.
heater_bias_len
a single value that specifies the length of the SQ1-bias heating pulses at the beginning of every new row period. heater_bias_len is measured from the first clock cycle of each new row dwell time. However, it takes 4 clock cycles to apply all the heater biases. This means the heater biases are applied by clock cycle #5.
enbl_mux

set enbl_mux = 3 for this special multiplexing mode.

Note 1: these commands are only available in AC firmware 2.0.9 and 5.0.2.
Note 2: bias_start parameter is not taken into account in this special multiplexing mode.

Here is a timing diagram of SQ1 Bias when enbl_mux = 3 Ac enbl mux 3 scheme.png